Question 1

Secondary power shall automatically provide power to a protected premises system within how many seconds after the primary power fails?

Options:

A.

10

B.

30

C.

60

D.

90

Question 2

Load testing of the control unit's VRLA batteries reveals that they must be replaced. Which two of the following are requirements for the replacement of VRLA batteries? (Choose two.)

Options:

A.

Batteries shall be approved by the authority having jurisdiction.

B.

Batteries shall be listed by a nationally recognized testing laboratory.

C.

Batteries shall be marked with the month and year of manufacture.

D.

Batteries shall be the same make and model as those being replaced.

Question 3

Inspection records for all systems shall be kept for which length of time?

Options:

A.

6 months

B.

5 years

C.

Until AHJ reviews records and 1 year

D.

Until the next test and 1 year

Question 4

Which three of the following test methods are used to ensure that the smoke detectors are within their sensitivity range? (Choose three.)

Options:

A.

AHJ approved calibrated test

B.

Listed control equipment arranged for testing

C.

Manufacturer's calibrated sensitivity test instrument

D.

Test approved by the engineer

Question 5

What is the testing frequency of an engine driven generator?

Options:

A.

Weekly

B.

Monthly

C.

Semiannually

D.

Annually

Question 6

Which of the following situations is considered an impairment?

Options:

A.

Closed sprinkler valve

B.

Intelligible audibility

C.

Smoke detector within 4 feet of a return air opening

D.

Smoke detector within 4 feet of an air supply diffuser

Question 7

According to NFPA 72, manual fire alarm boxes shall be located within which distance of each exit doorway on each floor?

Options:

A.

5 feet (1.5 meters)

B.

6 feet (2.0 meters)

C.

16 feet (5.0 meters)

D.

33 feet (10.0 meters)

Question 8

The fire alarm control unit shows a supervisory signal on the display. What is the possible cause?

Options:

A.

A duct smoke detector is in alarm.

B.

A manual fire alarm box has been activated.

C.

A spot smoke detector is in alarm.

D.

A waterflow alarm has been activated.

Question 9

What is the testing frequency of a remote annunciator?

Options:

A.

Monthly

B.

Quarterly

C.

Semiannually

D.

Annually

Question 10

The inspection phase, as opposed to the testing phase, of system control equipment should concentrate on which of the following tasks?

Options:

A.

Activation of all initiating devices

B.

Operational reliability only

C.

Proof of signals at monitoring facility

D.

Visual inspection only

Question 11

Which three of the following are how a McCulloh transmitter should be inspected? (Choose three.)

Options:

A.

Distinct waterflow condition

B.

Physical condition

C.

System normal condition

D.

Verify location

Question 12

Which two of the following are needed to perform a periodic test of a projected beam type smoke detector? (Choose two.)

Options:

A.

Blocking the transmitter

B.

Introducing smoke

C.

Using a listed test switch

D.

Using an optical filter

Question 13

Which three of the following branch circuit characteristics are required for circuit identification and accessibility of the fire alarm equipment's primary power supply? (Choose three.)

Options:

A.

The system circuit disconnect shall be permanently identified as "Fire Alarm."

B.

The system circuit disconnect shall be permanently identified at the control unit.

C.

Where a circuit breaker is the disconnecting means, a breaker locking device shall be installed.

D.

Where a circuit breaker is the disconnecting means, a breaker locking device shall be labeled.

Question 14

Secondary power for the fire alarm primary power supply shall be tested under which load?

Options:

A.

Half load

B.

Maximum load

C.

Minimum load

D.

Supervisory load

Question 15

When testing initiating devices, what is the maximum allowed time for the supervising station to verify receipt of the signal?

Options:

A.

60 seconds

B.

80 seconds

C.

90 seconds

D.

120 seconds

Question 16

When a system must be fully or partially disabled for less than 8 hours, who must be notified when the system is restored?

Options:

A.

AHJ

B.

Fire department

C.

Insurance company

D.

System owner

Question 17

A disconnection of the primary phone line shall cause which of the following events to occur?

Options:

A.

Activation of notification appliance

B.

Local annunciation only

C.

Notification via secondary phone line

D.

Supervisory condition

Question 18

How is a lead-acid battery inspected?

Options:

A.

By checking for damage

B.

By checking voltage

C.

By verifying specific gravity

D.

By verifying the charging circuit

Question 19

How often should radio transmitters be inspected?

Options:

A.

Monthly

B.

Quarterly

C.

Semiannually

D.

Annually

Question 20

How should the documentation cabinet be labeled?

Options:

A.

Fire alarm documents

B.

Fire alarm record documents

C.

System records

D.

System record documents

Question 21

Which two of the following should occur when a signal silence switch for a notification alarm is activated? (Choose two.)

Options:

A.

Audible appliances are deactivated.

B.

Door holders are deactivated.

C.

HVAC shutdown is deactivated.

D.

Visible appliances are deactivated.

Question 22

After 15 years from initial installation, all fixed-temperature, nonrestorable heat detectors shall be replaced or have how many detectors per 100 laboratories tested?

Options:

A.

2

B.

4

C.

6

D.

8

Question 23

Verification of a DACT’s trouble signal to the fire alarm shall be received within a maximum of how many minutes when the primary telephone line is disconnected?

Options:

A.

2

B.

3

C.

4

D.

5

Question 24

When the main power is disconnected, how long should a power supply with emergency voice communication systems work in alarm mode?

Options:

A.

Maximum of 5 minutes

B.

Maximum of 15 minutes

C.

Minimum of 5 minutes

D.

Minimum of 15 minutes

Question 25

How often are manual fire alarm boxes inspected?

Options:

A.

Monthly

B.

Quarterly

C.

Semiannually

D.

Annually